Trane RTPRC002-EN Air Conditioner User Manual


 
48
RT-PRC002-EN
Table PD-39— Hot Gas Reheat Temperature Rise
1,2,3
Leaving Evaporator Dry Bulb [F]
1
Tons SCFM 35 40 45 50 55 60 65
2500 23.4 23.8 25.0 26.9 29.5 32.9 37.0
3000 21.4 21.6 22.5 24.0 26.0 28.7 31.9
3500 19.5 19.7 20.4 21.5 23.1 25.2 27.7
12½ 4000 17.8 18.1 18.6 19.6 20.9 22.5 24.5
4500 16.3 16.7 17.3 18.1 19.2 20.5 22.1
5000 14.9 15.5 16.2 17.1 18.0 19.2 20.4
5500 13.5 14.4 15.3 16.2 17.2 18.1 19.1
6000 12.1 13.4 14.6 15.7 16.7 17.6 18.3
Tons SCFM 35 40 45 50 55 60 65
3000 34.4 36.7 38.9 41.2 43.5 45.8 48.1
3600 29.3 31.2 33.1 35.0 36.9 38.8 40.8
4200 25.4 27.0 28.6 30.2 31.9 33.5 35.1
15 4800 22.3 23.7 25.1 26.5 27.9 29.3 30.7
5400 19.9 21.2 22.4 23.7 24.9 26.2 27.4
6000 18.0 19.1 20.3 21.4 22.5 23.7 24.8
6600 16.4 17.5 18.6 19.6 20.7 21.7 22.8
7200 15.1 16.1 17.1 18.1 19.1 20.1 21.1
Tons SCFM 35 40 45 50 55 60 65
4000 22.0 22.5 23.6 25.4 27.7 30.6 34.0
4800 19.1 19.8 20.9 22.3 24.0 26.1 28.5
5600 16.6 17.4 18.4 19.5 20.9 22.4 24.0
20 6400 14.7 15.5 16.3 17.2 18.2 19.3 20.6
7200 13.5 14.1 14.7 15.4 16.2 17.0 17.9
8000 12.9 13.2 13.7 14.2 14.8 15.5 16.2
8800 12.5 12.9 13.3 13.7 14.2 14.8 15.4
9600 12.4 12.8 13.1 13.5 13.9 14.5 15.0
Notes:
1. Temperature does not account for indoor fan heat.
2. 70 deg OD Ambient Temperature.
3. For units with the Dehumidification (Hot Gas Reheat) option.
Performance
Data