15
RT-PRC002-EN
(12½, 15 Ton)
High Efficiency
General
Data
12½ Ton 15 Ton
Downflow and Horizontal Downflow and Horizontal
TC*151C3,C4,CW TC*181C3,C4, CW
Cooling Performance
1
Gross Cooling Capacity 154,000 189,000
EER
2
11.3 11. 5
8
Nominal CFM / ARI Rated CFM 5,000/4,400 6,000/5,300
ARI Net Cooling Capacity 146,000 180,000
Integrated Part Load Value
3
11.5 13.3
System Power KW 12.92 15.65
3
Compressor
No./Type 2/Scrolls 2/Scrolls
Sound Rating (BELS)
4
9.2 9.2
Outdoor Coil — Type Hi-Performance Hi-Performance
Tube Size (in.) O.D. 0.375 0.375
Face Area (sq ft) 27.12 35.30
Rows/FPI 3/16 3/16
Indoor Coil — Type Hi-Performance Hi-Performance
Tube Size (in.) 0.375 0.375
Face Area (sq ft) 17.50 26.00
Rows/FPI 3/15 3/15
Refrigerant Control Short Orifice
9
Short Orifice
8
Drain Connection No./Size (in.) 1/1.0 NPT 1/1.0 NPT
Outdoor Fan — Type Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26
Drive Type/No. Speeds Direct/1 Direct/1
CFM 10,400 11,000
No. Motors/HP 2/.50 2/.50
Motor RPM 1100 1100
Indoor Fan — Type FC Centrifugal FC Centrifugal
No. Used 1 1
Diameter x Width (in.) 15 x 15 18 x 18
Drive Type/No. Speeds BELT/1 BELT/1
No. Motors 1 1
Motor HP (Standard/Oversized) 3.0/5.0 3.0/5.0
Motor RPM (Standard/Oversized) 1740/3450 1740/3450
Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T
Filters — Type/Furnished? Throwaway/Yes
8
Throwaway/Yes
8
(No.) Size Recommended (in.) (2)20 x 20 x 2 (4) 20 x 20 x 2
(4)20 x 25 x 2 (4) 20 x 25 x 2
Optional Hot Gas Reheat Coil — Type Hi-Performance Hi-Performance
Tube Size (in.) OD 0.375 0.375
Face Area (sq. ft.) 17.5 26
Rows/FPI 1/16 1/16
Refrigerant Charge (Lbs of R-22)
5
/Circuit
Standard 15.0/13.8
9
25.0/13.0
8
Optional Hot Gas Reheat Coil 15.3/14.3 27.8/11.4
Notes:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net
and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment certification
program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Face area for Indoor Coil on horizontal models is 12.36.
7. Horizontal models have 4 - 20 x 25 x 2 filters.
8. Optional two inch pleated filters are also available for 12½ ton models.
9. TXV/Face-Split Option (Downflow Only) TCD151C3,4,W (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 13.4/12.0.
*Indicates both downflow and horizontal units.
Table GD - 3 — General Data