Trane PTEC1501GCA Air Conditioner User Manual


 
9PTAC-PRC001-EN
Performance
Data
Table PD-3 — Heat Pump Reverse Cycle Heating Capacity (Btu)
Model No.
1
PTHC 07 PTHC 09 PTHC 12 PTHC 15
Voltage
3
208 230 265 208 230 265 208 230 265 208 230 265
Amps 3.0 2.6 2.2 3.6 3.2 2.6 5.1 4.5 3.9 6.3 5.7 5.4
Watts 550 570 570 730 740 740 1000 1020 1020 1380 1390 1390
Btu
2
6200 6400 6400 8000 8100 8100 10600 10800 10800 13500 13300 13300
COP
2
3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.1 2.8 2.8 2.8
cfm (dry) 230 235 235 230 235 235 290 310 310 335 345 345
Heating
2
Btu °F
Outdoor Ambient 62 8200 8400 8400 10200 10300 10300 13000 13200 13200 16300 16400 16400
57 7600 7800 7800 9600 9700 9700 12200 12400 12400 15300 15400 15400
52 6900 7100 7100 8900 9000 9000 11400 11600 11600 14200 14300 14300
47 6200 6400 6400 8000 8100 8100 10600 10800 10800 13200 13300 13300
Rating Point (COP) 3.3 3.3 3.3 3.2 3.2 3.2 3.1 3.1 3.1 2.8 2.8 2.8
2
42 5500 5700 5700 7200 7300 7300 9800 10000 10000 12200 12300 12300
37 4900 5100 5100 6400 6500 6500 9000 9200 9200 11200 11300 11300
32 4300 4500 4500 5600 5700 5700 8200 8400 8400 10100 10200 10200
Watts 62 730 745 745 935 940 940 1230 1245 1245 1705 1715 1715
Outdoor Ambient 57 675 690 690 880 890 890 1150 1170 1170 1600 1610 1610
52 610 630 630 815 825 825 1075 1095 1095 1485 1495 1495
47 550 570 570 730 740 740 1000 1020 1020 1380 1390 1390
42 490 505 505 660 670 670 925 945 945 1275 1285 1285
37 435 450 450 585 595 595 850 870 870 1170 1180 1180
32 380 400 400 510 520 520 775 795 795 1055 1065 1065
Notes:
1. All 265 volt models must use Trane’s subbase or Trane’s hard-wire junction box kit.
2. Heating capacity and efficiency is based on unit operation without condensate pump. Unit automatically switches to electric heat at 25°F outdoor coil temperature.
Depending upon relative humidity conditions, this will occur at approximately 35 degrees outdoor ambient temperature.