Trane PTEC1501GCA Air Conditioner User Manual


 
PTAC-PRC001-EN8
Table PD-1 — Cooling Performance — Air Conditioner with Electric Heat Models
Model Type Air Conditioner
Model No.
1 & 5
PTEC 07 PTEC 09 PTEC 12 PTEC 15
Voltage
3
208 230 265 208 230 265 208 230 265 208 230 265
Capacity (Btu)
6
7000 7100 7100 8900 9100 9100 11900 12000 12000 14000 14200 14200
Amps 3.0 2.8 2.3 3.8 3.7 3.0 5.0 5.0 4.3 6.9 6.9 5.9
Watts 600 610 610 785 805 805 1110 1110 1130 1520 1545 1525
EER 11.6 11.6 11.6 11.3 11.3 11.3 10.7 10.7 10.7 9.2 9.2 9.3
Unit without Electric Heater
Min. Circuit/Ampacity
2 & 4
4.0 4.0 3.6 5.1 5.1 4.4 6.4 6.4 6.4 8.4 8.4 7.4
cfm (cool, wet coil)
High 240 245 245 240 245 245 325 315 325 315 325 325
Low 205 220 220 205 220 220 250 220 250 220 250 250
cfm (dry coil)
High 260 265 265 260 265 265 345 335 345 335 345 345
Low 215 230 230 215 230 230 265 235 265 235 265 265
Ventilated Air, cfm (fan only) 65* 65* 65* 65* 65* 65* 70* 70* 70* 70* 70* 70*
Dehumidification (pints/hr.) 1.6 1.6 1.6 2.6 2.6 2.6 3.5 3.5 3.5 4.4 4.4 4.4
Net wt. (approximate lbs.) 90 90 90 95 95 95 105 105 105 110 110 110
Shipping wt. (approximate lbs.) 105 105 105 110 110 110 120 120 120 125 125 125
* 95 cfm with optional power vent kit. Actual vent cfm performance will vary due to application and installation conditions.
Table PD-2 — Cooling Performance —Heat Pump with Electric Heat Models
Model Type Heat Pumps
Model No.
1 & 5
PTHC 07 PTHC 09 PTHC 12 PTHC 15
Voltage
3
208 230 265 208 230 265 208 230 265 208 230 265
Capacity(Btu)
6
7000 7100 7100 8800 9000 9000 11800 12000 12000 13800 14000 14000
Amps 3.0 2.8 2.3 3.8 3.5 3.0 5.0 4.6 4.3 6.9 6.3 5.9
Watts 610 615 615 785 805 805 1110 1120 1120 1485 1505 1505
EER 11.5 11.5 11.5 11.2 11.2 11.2 10.7 10.7 10.7 9.3 9.3 9.3
Unit without Electric Heater
Min Circuit/Ampacity
2 & 4
4.0 4.0 3.6 5.1 5.1 4.4 7.3 7.3 5.7 8.4 8.4 7.4
cfm (cool, wet coil)
High 240 245 245 240 245 245 315 325 325 315 325 325
Low 205 220 220 205 220 220 220 250 250 220 250 250
cfm (dry coil)
High 260 265 265 260 265 265 335 345 345 335 345 345
Low 215 230 230 215 230 230 235 265 265 235 265 265
Ventilated Air, cfm (fan only) 65* 65* 65* 65* 65* 65* 70* 70* 70* 70* 70* 70*
Dehumidification (pints/hr.) 1.6 1.6 1.6 2.6 2.6 2.6 3.5 3.5 3.5 4.4 4.4 4.4
Net wt. (approximate lbs.) 95 95 95 100 100 100 110 110 110 115 115 115
Shipping wt. (approximate lbs.) 110 110 110 115 115 115 125 125 125 130 130 130
*95 cfm with optional power vent kit. Actual vent cfm performance will vary due to application and installation conditions.
Notes:
1. All 265 volt models must use Trane’s subbase or Trane’s hard-wire junction box kit.
2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
3. Minimum voltage on 208/230 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included and
factory installed on Trane chassis). Note: All heat pump units must have electric coils.
5. Minimum operating ambient = 45°F.
6. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI standard 310/380.
EER — Energy Efficiency Ratio per American Refrigeration Institute (ARI) Test Procedures.
COP — Coefficient of Performance per ARI Test Procedures.
Performance
Data