Trane SCWG 020, SCWG 025, SCWG 030, SCWG 035, SWG 020, SWG 025, SWG 030, SWG 035, SCRG 020, SCRG 025, SCRG 032, SRG 020, SCRG 025, SCRG 032 Heating System User Manual


 
62 SCXG-SVX01B-EN
Connecting to Tracer Summit
®
IntelliPak
®
self-contained units operate
with Trane building automation software,
Tracer Summit
®
version 10.0.4 or later or
any OS2 operating system.
Tape the non-insulated end of the
shield on shielded wire at the
unit. Any connection between the
shield and ground will cause a
malfunction. If daisy-chained in
the unit, splice and tape the
shields to prevent contact with
ground.
ƽƽ
ƽƽ
ƽ
CAUTION
!
Pre-Startup
Requirements
Communication Wiring
Note: Communication link wiring is a
shielded, twisted pair of wire and must
comply with applicable electrical codes.
An optional communication link provides
a serial communication interface (SCI)
between Tracer Summit
®
and each
commercial self-contained (CSC) unit in
the system. The CSC system can have a
maximum of 12 CSC units per connection
link to Summit
®
. Use a single 18 AWG
shielded, twisted pair wire with stranded,
thinned copper conductors to establish
each communication link between
Summit
®
and each unit.
Installation