Trane 4YCY4024A Heat Pump User Manual


 
10
Performance Data Cooling
4YCY4048A1/3 AT 1600 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
85
59 45.3 38.2 42.9 45.3 45.3 3.6
63 47.2 31.0 35.7 40.5 43.7 3.6
67 50.9 24.4 29.1 33.9 37.1 3.7
71 55.0 17.7 22.5 27.3 30.4 3.7
95
59 42.7 37.0 41.7 42.7 42.7 3.9
63 44.5 29.8 34.6 39.3 42.6 4.0
67 48.0 23.2 28.0 32.8 36.0 4.0
71 51.8 16.7 21.4 26.2 29.4 4.0
105
59 40.1 35.8 40.1 40.1 40.1 4.3
63 41.8 28.7 33.5 38.3 41.4 4.4
67 45.0 22.2 27.0 31.7 34.9 4.4
71 48.6 15.6 20.4 25.1 28.3 4.4
115
59 37.5 34.7 37.5 37.5 37.5 4.7
63 39.1 27.7 32.4 37.2 39.1 4.7
67 42.1 21.1 25.8 30.6 33.8 4.8
71 45.5 14.5 19.3 24.0 27.2 4.8
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW CAPACITY TOTAL POWER
RATE, CFM MULTIPLIER MULTIPLIER
LOW 1400 0.97 0.98
HIGH 1800 1.03 1.02
ARI RATING FOR COOLING
CFM CAPACITY (A) TEST SEER EER
1605 48000 14.20 11.90
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
4YCY4060A1/3 AT 2000 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
85
59 56.5 47.6 53.5 56.5 56.5 4.4
63 58.9 38.5 44.5 50.5 54.4 4.4
67 63.5 30.2 36.2 42.2 46.2 4.5
71 68.5 21.9 27.8 33.8 37.8 4.5
95
59 53.1 46.0 52.0 53.1 53.1 4.8
63 55.4 37.0 43.1 49.0 53.0 4.9
67 59.7 28.8 34.8 40.7 44.8 5.0
71 64.4 20.5 26.4 32.4 36.4 5.0
105
59 49.7 44.5 49.7 49.7 49.7 5.3
63 51.9 35.7 41.6 47.6 51.6 5.3
67 55.9 27.4 33.3 39.3 43.3 5.4
71 60.3 19.1 25.0 31.0 35.0 5.4
115
59 46.4 43.0 46.4 46.4 46.4 5.8
63 48.3 34.2 40.2 46.2 48.3 5.8
67 52.1 26.0 32.0 37.9 41.9 5.9
71 56.2 17.7 23.7 29.6 33.7 5.9
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW CAPACITY TOTAL POWER
RATE, CFM MULTIPLIER MULTIPLIER
LOW 1750 0.97 0.98
HIGH 2250 1.03 1.02
ARI RATING FOR COOLING
CFM CAPACITY (A) TEST SEER EER
1799 58500 14.00 11.90
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.
4YCY4042A1 AT 1400 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD ID TOT SENS CAP AT ENTERING DB TEMP TOTAL
AMB WB CAP 72 75 78 80 KW
85
59 40.3 34.1 38.4 40.3 40.3 3.1
63 42.0 27.7 31.9 36.2 39.0 3.1
67 45.3 21.8 26.1 30.3 33.2 3.2
71 48.9 15.9 20.2 24.4 27.3 3.2
95
59 37.6 32.9 37.2 37.6 37.6 3.4
63 39.2 26.6 30.8 35.1 37.9 3.5
67 42.2 20.7 24.9 29.2 32.0 3.5
71 45.6 14.8 19.1 23.3 26.2 3.5
105
59 34.9 31.7 34.9 34.9 34.9 3.8
63 36.4 25.4 29.7 33.9 36.4 3.8
67 39.2 19.6 23.8 28.1 30.9 3.8
71 42.3 13.7 18.0 22.2 25.1 3.8
115
59 32.2 30.5 32.2 32.2 32.2 4.1
63 33.6 24.3 28.6 32.8 33.6 4.1
67 36.2 18.5 22.7 26.9 29.8 4.2
71 39.0 12.6 16.8 21.1 23.9 4.2
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW CAPACITY TOTAL POWER
RATE, CFM MULTIPLIER MULTIPLIER
LOW 1225 0.97 0.98
HIGH 1575 1.03 1.02
ARI RATING FOR COOLING
CFM CAPACITY (A) TEST SEER EER
1360 42000 14.25 12.00
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F
WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High
Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air
entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating
is the same as for cooling.