Trane 4TWB3 Heat Pump User Manual


 
6 18-BC61D1-1
Installer’s Guide
SUBCOOLING CHARGING IN COOLING ABOVE 55°F OD AMBIENT
SUBCOOLING CHARGING BELOW 55°F OD AMBIENT – IN HEATING ONLY
The Trane company has always recommended installing
Trane approved
matched indoor and outdoor systems.
All Trane split systems are ARI rated with only TXV indoor
systems.
The benefits of installing approved indoor and outdoor split
systems are maximum efficiency, optimum performance and
the best overall system reliability.
The following charging methods are therefore
prescribed for systems with indoor TXVs.
1. Subcooling (in the cooling mode) is the only
recommended method of charging above
55°F ambient temperatures.
2. For best results - the indoor temperature
should be kept between 70°F to 80°F. Add
system heat if needed.
3. At start-up, or whenever charge is removed
or added, the system must be operated for a
minimum twenty (20) minutes to stabilize
before accurate measurements can be made.
4. Measure Liquid Line Temperature and
Refrigerant Pressure at service valves.
5. Determine total refrigerant line length,
and height (lift) if indoor section is above
the condenser.
6. Determine the Design Subcool Charging
Temperature from the unit nameplate.
7. Locate this value in the appropriate column
of the Subcooling Charging Table. Locate
your liquid line temperature in the left
column of the table, and the intersecting
liquid line pressure under your nameplate
subcool value column. Add refrigerant to
raise the pressure to match the table, or
SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE
60
50
40
30
25
Add 10 psig to Subcool Charging Table Pressure
20
15
Use Design Subcool Value from Table
10
0
Subtract 10 psig from S.C. Table Pressure
10 20 25 30 40 60 80
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT
LINE LIFT (FEET)
1. The Subcool Charging Method in cooling is not recom-
mended below 55°F outdoor ambient.
2. The only recommended method of charging at outdoor
ambients below 55°F, is to weigh in the charge
in the
heating mode.
3. Use Nameplate charge plus standard charge adders for
line length.
4. Check liquid line temperature and pressure (at the
OD valves) to obtain a minimum of 10°F subcooling.
5. Add charge if a minimum of 10°F subcooling is not obtained
with the nameplate charge plus line length correction.
6. It is important to return in the spring or summer to
accurately charge the system in the cooling mode at
outdoor ambients above 55°F.
8 9 10 11 12 13 14
55 179 182 185 188 191 195 198
60 195 198 201 204 208 211 215
65 211 215 218 222 225 229 232
70 229 232 236 240 243 247 251
75 247 251 255 259 263 267 271
80 267 271 275 279 283 287 291
85 287 291 296 300 304 309 313
90 309 313 318 322 327 331 336
95 331 336 341 346 351 355 360
100 355 360 365 370 376 381 386
105 381 386 391 396 402 407 413
110 407 413 418 424 429 435 441
115 435 441 446 452 458 464 470
120 464 470 476 482 488 495 501
125 495 501 507 514 520 527 533
R-410A REFRIGERANT CHARGING CHART
Refer to Service Facts or
Installer's Guide for charging method.
LIQUID
TEMP
(
˚
F)
DESIGN SUBCOOLING (
˚
F)
LIQUID GAGE PRESSURE (PSI)
From Dwg. D154557P01 Rev. 2
remove refrigerant to lower the pressure. Again, wait
twenty (20) minutes for the system conditions to stabilize
before adjusting charge again.
8. When system is correctly charged, you can refer to
System Pressure Curves (in Service Facts) to verify
typical performance.