8-3. Optional Connector Specifications of Indoor P.C. Board
This option is not provided to oversea models.
Function
Humidifier output ()
Intilation output
HA
Option output
Outside error input
AUTO up/down grille
()
FILTER
Option error /
Humidifier setting ()
CHK
Operation check
DISP
Exhibition mode
EXCT
Demand
Connector No.
CN66
CN32
CN61
CN60
CN80
CN20
CN70
CN71
CN72
CN73
Pin No.
1
2
1
2
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
1
2
3
4
5
1
2
1
2
1
2
1
2
Specifications
DC12V
Output (Open collector)
DC12V
Output (Open collector)
ON/OFF input
0V
Remote controller prohibited input
Operation output (Open collector)
DC12V
Warning output (Open collector)
DC12V
Defrost output (Open collector)
Thermostat ON output (Open collector)
Cooling output (Open collector)
Heating output (Open collector)
Fan output (Open collector)
DC12V
NC
Outside error input
DC12V
Panel operation input
Panel up output (Open collector)
Panel down output (Open collector)
0V
0V
0V
0V
Demand input
0V
Remarks
Humidifier output is ON when heating operation is performed, when thermostat is on, when the fan is on.
The setting of Humidifier provided + Drain pump ON is performed by short-circuit of CN70 or from the
remote controller. (DN [40] = 0001)
Setting at shipment: Interlock of ON by indoor unit operation, with OFF by stop operation
The single operation setting by FAN button on the remote controller is performed on the remote
controller (DN [31] = 0000 0001)
HA ON/OFF input (J01: YES/NO=Pulse (At shipment from factory) /Static input selection)
Permission/Prohibition of remote controller operation stop is performed by input.
Operation ON (Answer back of HA)
Warning output ON
ON when outdoor unit is defrosted
ON when real thermostat is on. (Compressor ON)
ON when operation mode is cooling system (COOL, DRY, Cooling/Heating automatic cooling)
ON when operation mode is heating system (HEAT, Cooling/Heating automatic heating)
ON when indoor fan is on. (When air cleaner is used) OFF while clean operation is performed.
Generate the warning code “L30” (continuously for 1 minute) and stop the operation forcibly.
The grille is controlled according to up/down operation from the remote controller.
Setting of automatic up/down grille provided is performed on the remote controller.
(DN [30] = 0000 0001)
Selection of option error input (Protective operation display of device attached to outside) or Humidifier
setting input (Vaporizing + Drain pump ON)
Humidifier is set at shipment from factory.
Setting of option error input is performed on the remote controller. (DN [2A] = 0002 0001)
This check is used to check indoor operation. (Performs operation of indoor fan “H”, Louver horizontal
and Drain pump ON without communication with outdoor and remote controller)
Communication is available by indoor unit and remote controller only.
Indoor unit forced thermostat OFF operation