Toshiba RAV-SP360AT2-UL Air Conditioner User Manual


 
– 72 –
Resistance (kΩ)
(122˚F (50˚C) or lower)
Resistance (kΩ)
(122˚F (50˚C) or higher)
(0)
32
0
50
100
150
200
0
5
10
15
20
(10)
50
(20)
68
(30)
86
(40)
104
(50)
122
(60)
140
(70)
158
(80)
176
(90)
194
(100)
212
Temperature ˚F (˚C)
Resistance (kΩ)
(0)
32
0
10
20
30
40
(10)
50
(20)
68
(30)
86
(40)
104
(50)
122
(60)
140
(70)
158
(80)
176
(90)
194
(100)
212
Temperature ˚F (˚C)
Temperature sensor Temperature – Resistance value characteristic table
TA, TC, TCJ, TE, TS, TO sensors
Representative value
TD, TL sensors
Representative value
TA, TC, TCJ, TE, TS, TO sensors
TD, TL sensors
As TH sensor (Outdoor unit heat sink temp. sensor) is incorporated in the outdoor control P.C. board, the resistance
value cannot be measured.
Temperature
°F (°C)
32 ( 0)
50 ( 10)
68 ( 20)
77 ( 25)
86 ( 30)
104 ( 40)
122 ( 50)
140 ( 60)
158 ( 70)
176 ( 80)
194 ( 90)
212 (100)
Resistance value (k
ΩΩ
ΩΩ
Ω)
(Minimum (Standard (Maximum
value) value) value)
32.33 33.80 35.30
19.63 20.35 21.09
12.23 12.59 12.95
9.75 10.00 10.25
7.764 7.990 8.218
5.013 5.192 5.375
3.312 3.451 3.594
2.236 2.343 2.454
1.540 1.623 1.709
1.082 1.146 1.213
0.7740 0.8237 0.8761
0.5634 0.6023 0.6434
Temperature
°F (°C
32 ( 0)
50 ( 10)
68 ( 20)
77 ( 25)
86 ( 30)
104 ( 40)
122 ( 50)
140 ( 60)
158 ( 70)
176 ( 80)
194 ( 90)
212 (100)
Resistance value (k
ΩΩ
ΩΩ
Ω)
(Minimum (Standard (Maximum
value) value) value)
150.5 161.3 172.7
92.76 99.05 105.6
58.61 62.36 66.26
47.01 49.93 52.97
37.93 40.22 42.59
25.12 26.55 28.03
17.00 17.92 18.86
11.74 12.34 12.95
8.269 8.668 9.074
5.925 6.195 6.470
4.321 4.507 4.696
3.205 3.336 3.468