Toshiba RAV-SP1404AT-E Air Conditioner User Manual


 
– 49 –
No.
6
Item
Air speed
selection
(Continued)
Outline of specifications
Remarks
Selection of high ceiling
type
Item code:
[5d] or selection of high
ceiling on P.C. board
SW501
However only when the
high ceiling selection is
set to [Standard]
[DRY] is displayed.
3) In heating operation, the mode changes to [UL] if thermostat
is turned off.
4) If Ta 25°C when heating operation has started and when
defrost operation has been cleared, the air conditioner
operates with (H) mode or higher mode for 1 minute after Tc
entered in E zone of cool air discharge preventive control
(Item 7).
5) In automatic cooling/heating operation, the revolution
frequency of (HH) is set larger than that in the standard
cooling/heating operation.
6) Dry clean operation
When performing dry operation after stopping the cooling
operation, the mode becomes [UL] (210 rpm).
Item code
[5d]
SW501 (1)/(2)
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
Standard Type 1 Type 3 Type 6
0136
OFF/OFF ON/OFF OFF/ON ON/ON
HEAT COOL HEAT COOL HEAT COOL HEAT COOL
HH HH HH HH
HH HH
H+ H+, H H+, H
H+, H H+, H
L+, L L+, L
H+
HH H
HH H L+ L+
H+ H+ L L
HL+
HL+L
L+ L
L+ L
L
UL UL UL UL
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
SM56 SM80 SM110 SM140
Revolution speed (rpm)
610 630 700 700
550 590 670 670
500 530 660 660
450 470 640 650
400 450 620 640
390 440 610 630
370 410 550 560
350 380 490 490
340 370 480 480
330 350 450 460
320 330 400 430
310 320 400 420
250 250 300 300
Ta
(˚C)
F4F5
F5
47
42
However the revolution
frequency is restricted in
the automatic heating
operation as shown in
the following figure.