– 111 –
DN
42
45
C2
CC
CD
D0
D1
D3
D4
F0
F1
F2
F3
F4
Item
Self-clean operation time
Selection of louver horizontal discharge
position
Current demand X% to outdoor unit
Setting of self-clean operation forced stop
Clean operation stop function when
[ON/OFF] operation is prohibited.
Existence of remote controller save function
Existence of 8°C heating operation function
Revolution frequency of self clean operation
Display / No display of
[Dry operation] during self clean operation
Louver swing mode
Louver No.1 fixed position
Louver No.2 fixed position
Louver No.3 fixed position
Louver No.4 fixed position
Contents
0000: None 0000: 0.5 h to 0.012: 0 h
Set when compressor-ON time is 10 to 60 minutes.
When ON-time is 60 minutes or more,
the double of this operation time setting is set.
0000: Smudging-less setting
0002: Cold draft preventive setting
0050: 50% to 0100: 100%
0000: No
• Clean operation is performed in case of stop by HA input.
• HA operation output OFF during clean operation in case of
stop by remote controller
0001: Yes
• Clean operation is not performed in case of stop by HA input.
• HA operation output ON during clean operation in case of stop
by remote controller
The air conditioner stops (including fire alarm such as remote
monitor system) while setup of [ON/OFF] operation prohibited
(Central 1, 2) is performed from the central controller side.
0000: Valid (Clean operation)
0001: Invalid (No clean operation)
0000: Invalid (Impossible) 0001: Valid (Possible)
0000: Invalid (Impossible) 0001: Valid (Possible)
0000: Invalid (Self clean operation is not carried out.)
0001: Valid (Self clean operation is practiced with 210 rpm.)
0000: Display 0001: No display
0000: No synchronization 0001: 4-way synchronization
0002: Dual 0003: Cycle
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
Downward discharge position
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
Downward discharge position
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
Downward discharge position
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
Downward discharge position
At shipment from factory
0002: 1 hour
0000: Smudging-
less setting
0075: 75%
0000: None
0000: Valid
0001: Valid (Possible)
0001: Invalid (Impossible)
0001: Valid
(210 rpm / operation)
0000: Display
0001: 4-way
synchronization
0000: Release
0000: Release
0000: Release
0000: Release
∗ The swing mode selection (DN code No. [F0]), louver fix (DN code No. [F1] to [F4]) and restriction ratio setting for
save operation (DN code No. [C2]) can be set/changed from the normal DN setup (Detail DN setup).