Power ON
“SETTING”
flashes
“SETTING”
goes out
Remote
controller
is available
Approx. 5 minutes
7. When installing separately sold filters
REQUIREMENT
When you use this air conditioner for the first time, it takes approx. 5 minutes until the remote controller becomes
available after power-on. This is normal.
<When power is turned on for the first time after installation>
It takes approx. 5 minutes until the remote controller
becomes available.
( Display content varies with the indoor unit model.)
∗∗
∗∗ ∗∗
-
Procedure 2
Each time you push
UNIT LOUVER
button, indoor unit
numbers in the control group change cyclically.
Select the indoor unit you want to change settings for.
The fan of the selected unit runs. You can confirm the
indoor unit for which you want to change settings.
4
6
1
5
1
3
2
Procedure 1
Push
TEST
button and temp. setup button
simultaneously for at least 4 seconds.
After a while, the display flashes as shown in the
figure. Confirm that the CODE No. is [01].
If the CODE No. is not [01], push
TEST
button to erase
the display content, and repeat the procedure from
the beginning.
(No operation of the remote controller is accepted for
a while after
TEST
button is pushed.)
Procedure 3
Using temp. setup / buttons, specify CODE
No. [
∗∗
].
Procedure 4
Using timer time / buttons, select SET DATA
[
∗∗∗∗
].
Procedure 5
Push
SET
button. When the display changes from
flashing to lit, the setup is completed.
To change settings of another indoor unit, repeat
from Procedure
2.
To change other settings of the selected indoor unit,
repeat from Procedure
3.
Use
SET
button to clear the settings.
To make settings after
SET
button was pushed, repeat
from Procedure
2.
Procedure 6
When settings have been completed, push
TEST
button
to determine the settings.
When
TEST
button is pushed, “SETTING” flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the
remote controller is accepted.)
Power ON
“SETTING”
flashes
“SETTING”
goes out
Remote
controller
is available
Approx. 1 minute
<When power is turned on for the second (or later) time>
It takes approx. 1 minute until the remote controller
becomes available.
Normal settings were made when the indoor unit
was shipped from factory. Change the indoor unit settings as required.
Use the wired remote controller to change the settings.
The settings cannot be changed using the wireless remote controller, sub remote controller, or remote-
controllerless system (for central remote controller only).
Therefore, install the wired remote controller to change the settings.
n Changing of settings of for applicable controls
Basic procedure for changing settings
Change the settings while the air conditioner is not working.