Toshiba RAV-SP1104AT-E Air Conditioner User Manual


 
– 140 –
Resistance (k) (50˚C or lower)
Resistance (k) (50˚C or higher)
0
0
50
100
150
200
0
5
10
15
20
10 20 30 40 50 60 70 80 90 100
Temperature (˚C)
Resistance (k)
0
0
10
20
30
40
10 20 30 40 50 60 70 80 90 100
Temperature (˚C)
Temperature sensor Temperature – Resistance value characteristic table
T A, T C, T CJ, T E, T S, T O sensors
Representative value
T D, T L sensors
Representative value
T A, T C, T CJ, T E, T S, T O sensors
T D, T L sensors
As TH sensor (Outdoor unit heat sink temp. sensor) is incorporated in the outdoor control P.C. board, the resistance
value cannot be measured.
T emperature
C)
0
10
20
25
30
40
50
60
70
80
90
100
Resistance value (k
)
(Minimum value) (Standard value) (Maximum value)
32.33 33.80 35.30
19.63 20.35 21.09
12.23 12.59 12.95
9.75 10.00 10.25
7.764 7.990 8.218
5.013 5.192 5.375
3.312 3.451 3.594
2.236 2.343 2.454
1.540 1.623 1.709
1.082 1.146 1.213
0.7740 0.8237 0.8761
0.5634 0.6023 0.6434
T emperature
C)
0
10
20
25
30
40
50
60
70
80
90
100
Resistance value (k
)
(Minimum value) (Standard value) (Maximum value)
150.5 161.3 172.7
92.76 99.05 105.6
58.61 62.36 66.26
47.01 49.93 52.97
37.93 40.22 42.59
25.12 26.55 28.03
17.00 17.92 18.86
11.74 12.34 12.95
8.269 8.668 9.074
5.925 6.195 6.470
4.321 4.507 4.696
3.205 3.336 3.468
<In case of SP40, SP45>