Toshiba RAV-SP1104AT8ZG-E Air Conditioner User Manual


 
– 37 –
5. SPECIFICATIONS OF ELECTRICAL PARTS
5-1. Outdoor Unit
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Parts name
Compressor
Outdoor fan motor
4-way valve coil
PMV coil
High pressure switch
Reactor
Reactor
Reactor
P.C. board (Compressor drive)
P.C. board (Fan motor drive)
P.C. board (Control)
P.C. board (Noise filter)
Outdoor temp. sensor (TO sensor)
Discharge temp. sensor (TD sensor)
Suction temp. sensor (TS sensor)
Heat exchanger sensor (TE sensor)
Heat exchanger mid. temp. sensor (TL sensor)
Fuse
Fuse (Mounted on P.C. board, MCC-1596)
Fuse (Mounted on P.C. board, MCC-1596)
Fuse (Mounted on P.C. board, MCC-1597)
Fuse (Mounted on P.C. board, MCC-1597)
Fuse (Mounted on P.C. board, MCC-1599)
Fuse (Mounted on P.C. board, MCC-1600)
Relay
Posistor
Compressor thermo.
Type
DA422A3F-27M
ICF-280-A100-1
STF-01AJ502E1
UKV-A038
ACB-4UB83W
CH-78
CH-68
CH-56
MCC-1596
MCC-1597
MCC-1599
MCC-1600
TLC 10A
GAC1 31.5A
SCT 3.15A
GDM 250V 15A
SCT 3.15A
FJL 250V 3.15A
ET 6.3A
EL200/240A2-F(M)
ZPR0YCE 101A 500
US-622
Specifications
DC 280 V, 100 W
AC 220 – 240 V, 50/60 Hz
DC 12 V
OFF : 4.15 MPa
4.2 mH, 16 A
18 mH, 5 A
5.8 mH, 18.5 A
10 kΩ at 25°C
50 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
10 A, 250 V
31.5 A, 500 V
T3.15 A, AC 250 V
15 A, 250 V
T3.15 A, AC 250 V
T3.15 A, AC 250 V
T6.3 A, AC 250 V
Contact : AC 480 V, 20A
100 Ω, 500 V
OFF : 125 ± 4 °C, ON : 60 ± 5 °C