Toshiba RAV-SP1104AT8-TR Air Conditioner User Manual


 
– 56 –
10. Defrost control
1) In heating operation, defrost operation is performed when TE sensor satisfies any condition in A zone to
D zone.
2) During defrosting operation, it finishes if TE sensor continued 12°C or higher for 3 seconds or continued
7°C TE < 12°C for 1 minute.
The defrost operation also finishes when it continued for 10 minutes even if TE sensor temperature was
7°C or lower.
3) After defrost operation was reset, the compressor stopped for approx. 40 seconds and then the heating
operation starts.
The minimum TE value and To value between 10 and 15 minutes after heating operation has started
are stored in memory as TEO and ToO, respectively.
4) The time of above d can be changed by
exchanging jumper [J805] with [J806] of the
outdoor control P.C. board.
(Setting at shipment: 150 minutes)
0 10 15 39 45 55 d
[min.]
TE [˚C]
–2
–5
–10
–23
A zone
A zone
B zone
B zone
C zone
C zone
D zone
D zone
A zone
B zone
C zone
D zone
Start of heating operation
J805 J806
¡¡
¡
×
×
¡
××
d
150 minutes
Setting at shipment
90 minutes
60 minutes
30 minutes
¡
: Short circuit,
×
: Open
A zone
B zone
C zone
D zone
In normal To In abnormal To
When status (TEO – TE) – (ToO – To) 3°C When status (TEO – TE) 3°C
continued for 20 seconds continued for 20 seconds
When status (TEO – TE) – (ToO – To) 2°C When status (TEO – TE) 2°C
continued for 20 seconds continued for 20 seconds
When status (TE –23°C) continued for 20 seconds
When compressor operation status of TE < –2°C is calculated by d portion
11. High-pressure switch/Compressor case thermostat control
1) When the high-pressure switch or the compressor case thermostat operates, the operation of the
compressor is terminated.
2) The compressor restarts after 5 minutes using [1] as an error count.
After restart, the error count is cleared when operation continues for 10 minutes or more.
3) An error is confirmed with the error count [10].
4) For the indicated contents of error, confirm using the check code table.