Toshiba RAV-SM802XT-E Air Conditioner User Manual


 
17
LOW
+
=
MED
+
=
LOW+MED
2
MED+HIGH
2
MODEL
RAV-SM562XT-E RAV-SM802XT-E
Motor speed Air flow level Motor speed Air flow level
(rpm) (m
3
/h) (rpm) (m
3
/h)
Cooling HIGH 1060 800 1190 900
and MED 950 690 1010 750
Fan only LOW 800 580 850 650
HIGH 1120 830 1300 980
Heating MED 970 730 1070 800
LOW 820 600 860 650
[FAN AUTO]
0.5
1
1.5
2
*1
*2
5.0
5.5
0
Preset
temp.
M
+
H
L
°C
(Room temp.) (Preset temp.)
<HEAT>
NOTE :
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in
motor speed between M+ and L.
Fig. 8-3-2
Table 8-3-1
8-4. Cool air discharge preventive control
In heating operation, the indoor heat exchanger
restricts revolving speed of the fan motor to prevent a
cold draft. The upper limit of the revolving speed is
shown in Fig. 8-4-1 and Table 8-4-1.
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF.
*2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24°C.
*3: SUL means Super Ultra Low.
*4: Calculated from difference in motor speed
between SUL and HIGH.
Fig. 8-4-1 Cold draft preventing control
*5 and *6:
Table 8-4-1
A+4 A+4
A8A8
46
45
34
33
33 21
32 20
*2
*6 *5
Manual
(One of
5 steps)
LH
(Up to
setting
speed)
AUTO
*4
SUL*
3
SUL*1
Stop
Fan *5 *6
speed Starting period Stabilized period
AUTO Up until 12 minutes
passed after starting
the unit
From 12 to 25 minutes
passed after starting
the unit and room
temperature is 3°C
lower than preset
temperature
Manual Room temperature
(L H) < Preset temperature
4°C
From 12 to 25 minutes
passed after starting
the unit and room
temperature is
between preset
temperature and 3°C
lower than preset
temperature
25 minutes or more
passed after starting
the unit
Room temperature
Preset temperature
3.5°C
FILE NO. SVM-06012