Function selection CODE No. (DN) list
∗ Restriction ratio setting for save operation (DODE No. (DN) [C2]) can be set/changed from the normal CODE No. (DN) setup
(Detail CODE No. (DN) setup).
CODE No.
(DN)
01
02
03
06
0C
0F
10
11
12
13
14
1E
28
2A
2b
2E
31
32
60
69
86
Item
Filter sign lighting time
Filter stain level
Central control address
Heating suction temp. shift
Preparing indication selection
Cooling-only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
In automatic cooling/heating, temp.
width of cool → heat, heat →
cool mode selection control point
Auto restart
Selection of option / error input
(CN80)
Selection of thermostat output
(T10
)
Selection of HA (T10
) terminal
Fan (Single operation)
Sensor selection
Timer setting
(Wired remote controller)
Louver setting for cooling
Correction of feeling
of strong heating
Contents
0000: None 0001: 150H
0002: 2500H 0003: 5000H
0004: 10000H 0005: Clogging sensor used
0000: Standard
0001: Heavy stain (Half of standard time)
0001: No.1 unit to 0064: No.64 unit
0099: Undecided
0000: No shift 0001: +1°C
0002: +2°C to 0010: +10°C
(Up to +6 is recommended.)
0000: Preparing indicated 0001: No indication
0000: Heat pump
0001: Cooling only (No display for [AUTO] [HEAT] )
0001: 4-way air discharge cassette
0004: Concealed duct
0007: Under ceiling 0008: High wall
0000: Undecided 0001 to 0034
0001: No.1 unit to 0030: No.30 unit
0001: No.1 unit to 0064: No.64 unit
0000: Individual 0001: Master unit in group
0002: Follower unit in group
0000: 0 deg to 0010: 10 deg
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0000: None 0001: Provided
0000: Filter input 0001: Alarm input
0002: External alarm input (Air cleaner, etc.)
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Normal (JEMA) 0001: Card input
0002: Fire alarm input (Forgotten to be off)
0000: Impossible 0001: Possible
0000: Body TA sensor
0001: Remote controller sensor
0000: Operable 0001: Operation prohibited
0000: Normal 0001: Down allowed
0000: Not priovided 0001: Priovided
At shipment
from factory
0001: 150H
0000: Standard
0099: Undecided
0002: +2°C
0000: Preparing indicated
0000: Heat pump
0008: High wall
According to capacity type
0099: Undecided
0099: Undecided
0099: Undecided
0003: 3 deg
(Ts±1.5)
0000: None
0002: External alarm input
0000: Thermostat ON
0000: Normal
(HA terminal)
0000: Impossible
0000: Body sensor
0000: Operable
0000: Normal
0000: Not priovided
FILE NO. SVM-12004
0003: +3°C
0003: +3°C
C2
Power saving
(Current demand X% to
0050 : 50% to 0100 : 100%
0075 : 75%
outdoor unit)
– 69 –