Toshiba RAV-SM2242DT-E Air Conditioner User Manual


 
– 34 –
Concealed Duct High Static Pressure
Installation Manual
EN
8°C Operation
Pre-heating operation can be set for cold regions where room
temperature drops to below zero.
Procedure 1
Push simultaneously + + buttons for 4 seconds
or more when the air conditioner is not working.
After a while, the display part flashes as shown below. Check
the Displayed CODE No. is [10].
When the CODE No. is other than [10], push button to
erase the display and repeat procedure from the first step.
(After pushing button, operation of the remote
controller is not accepted for approx. 1 minute.)
Procedure 2
Every pushing button, the indoor unit No. in the
group control is displayed in order. Select the indoor unit of
which setup is changed. In this time, the position of the indoor
unit of which setup is changed can be confirmed because fan
of the selected indoor unit operate.
Procedure 3
Using TEMP. / buttons, specify CODE No. [d1].
Procedure 4
Using TIME / buttons, select SET DATA [0001].
Procedure 5
Push button.
In this time, the setup finishes when the display changes from
flashing to lighting.
Procedure 6
Push button.(Setup is determined.)
When pushing button, the display disappears and the
status
Becomes the usual stop status. (When pushing button
the operation from the remote controller is not accepted for
approx. 1 minute.)
SET DATA 8°C Operation setting
0000
None
(Factory default)
0001
8°C Operation setting
(* Display changes according to
the model No. of indoor unit.)
34-EN