Toshiba RAV-SM2242DT-E Air Conditioner User Manual


 
– 29 –
Concealed Duct High Static Pressure
Installation Manual
Procedure 6
When settings have been completed, push button to
determine the settings.
When button is pushed, “SETTING” flashes and then the
display content disappears and the air conditioner enters the
normal stop mode.
(While “SETTING” is flashing, no operation of the remote
controller is accepted.)
Filter sign setting
According to the installation condition, the filter sign term
(Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
(
1 o 2 o 3 o 4 o 5 o 6).
For the CODE No. in Procedure
3, specify [01].
For the [SET DATA] in Procedure 4, select the SET DATA
of filter sign term from the following table.
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the room,
the detection temperature of heating can be raised. Also use
a circulator, etc. to circulate heat air near the ceiling.
Follow to the basic operation procedure
(
1 o 2 o 3 o 4 o 5 o 6).
For the CODE No. in Procedure
3, specify [06].
For the set data in Procedure 4, select the SET DATA of
shift value of detection temperature to be set up from the
table below.
Power saving mode
1. Push button for at least four seconds when
the air conditioner is not working.
flashes.
Indicates CODE No. “C2.”
2. Select an indoor unit to be set by pushing (left
side of the button).
Each time you push the button, unit numbers change as
follows:
The fan of the selected unit runs.
3. Adjust the power save setting by pushing TIME
buttons.
Each push of the button changes the power level by 1%
within the range from 100% to 50%.
* The factory default is 75%.
4. Determine the setting by pushing button.
5. Push button to complete the setting.
SET DATA Filter sign term
0000
None
0001
150H
0002
2500H
(Factory default)
0003
5000H
0004
10000H
SET DATA Detection temperature shift value
0000
No shift
0001
+1°C
0002
+2°C
(Factory default)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
UNIT No.
1-1
UNIT No.
1-2
UNIT No.
1-3
UNIT No.
1-4
Setting of power level in
power saving mode
29-EN