Toshiba RAV-SM2242DT-E Air Conditioner User Manual


 
– 12 –
Concealed Duct High Static Pressure
Installation Manual
EN
Installation of hanging bolt
Consider the piping/wiring after the unit is hung when
determining the location of the indoor unit installation and
orientation.
After the location of the indoor unit installation has been
determined, install hanging bolts.
For the dimensions of the hanging bolt pitches, refer to the
external view.
When a ceiling already exists, lay the drain pipe,
refrigerant pipe, system interconnection wires, and remote
controller wires to their connection locations before
hanging the indoor unit.
Procure hanging bolts washer and nuts for installing the
indoor unit (these are not supplied).
Installation of hanging bolt
Use M10 hanging bolts (4 pcs, to be local procure).
Matching to the existing structure, set pitch according to size
in the unit external view as shown below.
Installation of indoor unit
Treatment of ceiling
The ceiling differs according to structure of building.
For details, consult your constructor or interior finish
contractor.
In the process after the ceiling board has been removed, it is
important to reinforce ceiling foundation (frame) and to keep
horizontal level of installed ceiling correctly in order to
prevent vibration of ceiling board.
Attach the nuts and the M10 flat washers to the hanging
bolt.
Put washers at up and down of the hanging bracket of the
indoor unit to hang down the indoor unit.
Using a level vial, check that four sides are horizontal.
(Horizontal degree: Within 5mm)
Check that four sides are horizontal using a level vial.
(Horizontal degree: Within 5mm)
REQUIREMENT
Hang the unit in a horizontal position.
When unit is hanged to slant, it may cause overflow of
drainage.
Install the unit within the dimension according to the figure
below.
Using level vial or vinyl hose to confirm whether the unit
is hang horizontally.
Hanging bolt M10 or W3/8 4 pieces
Nut M10 or W3/8 12 pieces
Washer M10 8 pieces
New concrete slab
Install the bolts with insert brackets or anchor bolts.
Steel flame structure
Use existing angles or install new support angles.
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
Rubber
Anchor bolt
(Blade type
bracket)
(Slide type
bracket)
(Pipe hanging
anchor bolt)
Hanging bolt
Hanging bolt
Support angle
Nut
(W3/8 or M10)
M10 flat washer
M10 flat washer
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
0 to 5mm
±5mm
Set the air inlet and air
outlet sides are within
5mm with each other.
Water pouring
Set the drain pipe
connecting port side within
5mm lower than opposite
side.
Front view
Side view
Vinyl hose
12-EN