Toshiba RAV-SM1603ATZG-E Air Conditioner User Manual


 
– 98 –
[L09 error]
YES
YES
NO
NO
NO
NO
Check cause of operation.
Check central controller
(including network adapter).
Defect Replace
Check indoor P.C. board.
Defect Replace
YES
YES
YES
YES
YES
NO
NO
Do outside devices normally work?
Are outside devices of
connector CN80 connected?
Is the central controller
[98] displayed?
Is the indoor remote controller
[L20] displayed?
Is not the multiple same central
control system addresses connected?
Is not yet capacity setting
of indoor unit set up?
Are wiring connections
to communication lines
X and Y normal?
Set capacity data of indoor unit.
(Setup item code (DN)=11)
Check indoor P.C. board.
Defect Replace
Correct wiring connection.
Correct central control system address.
Check indoor P.C. board.
Defect Replace
Check outside devices.
Defect Replace
[L20 error]
[L30 error]