Toshiba RAV-SM1603ATZG-E Air Conditioner User Manual


 
– 105 –
[P29 error]
Is not earthed?
Is not winding opened?
Compressor error Replace
Correct connection of connector.
Replace TE and TS sensors.
Check and correct circuit cabling
such as cabling to compressor.
Check IPDU P.C. board.
Defect Replace
Check CDB.
Defect Replace
Refer to relational graph of temperature sensor resistance value
and temperature Characteristics-3.
Correct connection of connector.
Replace TD sensor.
Check control P.C. board.
Defect Replace
Refer to relational graph of temperature sensor resistance value
and temperature Characteristics-4.
Are connections of TE/TS sensor
connectors of CDB CN604/CN605 normal?
Are characteristics of TE/TS sensor
resistance values normal?
Is connection of TD sensor connector
of CDB CN600 normal?
Are characteristics of TD sensor
resistance value normal?
Is not winding shorted?
(Is resistance between windings 0.6 to 1.2?)
Is compressor normal?
Are connections of
cable/connector normal?
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
[F06 error]
[P04 error]