Toshiba RAS-M14EACV-E Air Conditioner User Manual


 
– 98 –
No.
1
11-9-3. Indoor Unit (Other Parts)
Part name
Room temp. (TA) sensor
Heat exchanger (TC) sensor
Checking procedure
Disconnect the connector and measure the resistance value with tester.
(Normal temp.)
Refer to 11-5-1. (5).
Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25°C)
Remote controller
Louver motor
MP24GA
2
3
Refer to 11-5-1. (3) and (4).Indoor fan motor4
5
4
3
2
1
White
Yellow
Yellow
Yellow
Yellow
5
4
3
2
1
No.
1
Red
White Black
11-9-4. Outdoor Unit
Part name
Compressor
(Model : DA111A1F-20F)
Checking procedure
Measure the resistance value of each winding by using the tester.
Resistance value
380 ± 40
Position
1 to 2
1 to 3
1 to 4
1 to 5
Temperature
Sensor
TA, TC (k)
10°C 20°C 25°C 30°C 40°C
20.7 12.6 10.0 7.9 4.5
Red
White Black
Check conduction by using the tester.Compressor thermo. Bimetal
type (Model : US-
622KXTMQO-SS)
4
Position
Red - White
White - Black
Black- Red
Resistance value
17 to 25k
17 to 25k
17 to 25k
Compressor
(Model : DA130A1F-25F)
Measure the resistance value of each winding by using the tester.2
Red
White Black
Outdoor fan motor
(Model : ICF-140-43-4)
Measure the resistance value of each winding by using the tester.3
Under 20°C
Position
Red - White
White - Black
Black- Red
Resistance value
0.88 to 0.98
0.88 to 0.98
0.88 to 0.98
Position
Red - White
White - Black
Black - Red
Under 20°C
0.69 to 0.77
Resistance value