– 34 –
Horizontal
blowing
Inclined
blowing
Blowing
downward
Air direction
Inclined
blowing
Horizontal
blowing
Powerful
Room temp. (Ta) < Set temp. (Tsc) + 3.5 Room temp. (Ta) ≥ Set temp. (Tsc) + 3.5
Initial setting of “Cooling storage position”
Louver : Directs downward (9˚)
Initial setting of “Cooling storage position”
Louver : Directs downward (9˚)
“Inclined blowing”
Louver : Directs downward (14˚)
Heating operation/
AUTO (HEAT)
ECO operation
Room temp. (Ta) < Set temp. (Tsc) – 3
or 25 minutes after start of operation
Room temp. (Ta) ≥ Set temp. (Tsc) – 3
Initial setting of “Heating storage position”
Louver : Directs downward (76˚)
“Heating storage position”
Louver : Directs downward (76˚)
“Cooling storage position”
Louver : Directs downward (9˚)
Cooling/AUTO
(COOL)/DRY operation
Powerful
operation
Cooling memory
position
Room temp. ≥ Set temp. +3.5
Cooling memory
position
Inclined
blowing
Room temp. ≥
Set temp. +3.5
YES
YES
NO
YES
NO
NO
Heating operation
ECO
operation
Heating memory
position
Horizontal
position
Heating memory
position
Room temp. ≥
Set temp. –3.0
Room temp. ≥ Set temp. –3.0
YES
YES
YES
NO
NO
NO
Louver angle
Horizontal
(0˚)
Item
9. Louver control
1) Louver
position
Operation flow and applicable data, etc.
This function controls the air direction of the indoor unit.
Description
• Swing operation is performed in width 35° with the stop position as
the center.
• If the stop position exceeds either upper or lower limit position,
swing operation is performed in width 35° from the limit which the
stop position exceeded.
3) Swing
2) Louver position in heating operation
• Swing
When pressing
[SWING] button during
operation, the louver
starts swinging.
• The position is automatically controlled according to the operation mode (COOL/HEAT).
• The set louver position is stored in memory by the microcomputer, and the louver returns to the
stored position when the next operation is performed. (Cooling/heating memory position)
The angle of the louver is indicated as the horizontal angle is 0°.
When the louver closes fully, it directs approx. 49° upward.
1) Louver position in cooling operation
2) Air direction adjustment
• The louver position can
be arbitrarily set up by
pressing [FIX] button.