Horizontal
blowing
Inclined
blowing
Blowing
downward
Air direction
Inclined
blowing
Horizontal
blowing
Initial setting of "Cooling storage position"
Louver : Directs downward (35.3°)
Heating operation/
AUTO (HEAT)
Initial setting of “Heating storage position”
Louver : Directs downward (80.5 )
Item
8. Louver control
1) Louver
position
Operation flow and applicable data, etc.
This function controls the air direction of the indoor unit.
Description
• Swing operation is perfor in range 35° with the Fixed position as
the center.
• If the swing range exceeded either upper or lower limit position,
swing operation is perfomed in range 35° from the limit.
3) Swing
2) Louver position in heating operation
2) Air direction adjustment
• The position is automatically controlled according to the operation
• The set louver position is stored in memory by the microcomputer,
The angle of the louver is indicated as the louver closes fully is 0°.
1) Louver position in cooling operation
mode (COOL/HEAT).
and the louver returns to the stored position when the next operation
is performed. (Cooling/Heating memory position)
• Swing
When pressing
[SWING] button during
operation, the louver
starts swinging.
• The louver position can
be arbitrarily set up by
pressing [FIX] button.
– 36 –
FILE NO. SVM-10019
Fixed
Position
before start
swing
Upper Limit
Position.
Lower Limit
Position
30
o
5
o
Swing
range 35
o
Upper Limit
Position.
Lower Limit
Position.
Fixed Position
before start
swing.
17.5
o
17.5
o
Swing
range 35
o