Toshiba RAS-10YKV-E Air Conditioner User Manual


 
– 56 –
Checking procedure
Disconnect the connector and measure the resistance value with tester.
(Normal temp.)
To item of How to judge whether remote controller is good or bad of the
Judgment of trouble by symptom.
Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25°C)
Since judgment of DC motor is difficult on the single motor, refer to 10-
5-1. (3).
No. Part name
1 Room temp. (TA) sensor
Heat exchanger (TC) sensor
2 Remote controller
3 Louver motor
MP35EA7
4 Indoor fan motor
Position Resistance value
1 to 4
1 to 6
130 ± 10
2 to 3
2 to 5
Temperature
10°C 20°C 25°C 30°C 40°C
Sensor
TA, TC (k) 20,7 12,6 10,0 7,9 4,5
No. Part name
1 Compressor
(Model : DA91A1F-44F)
2 Outdoor fan motor
(Model : ICF-140-40-7)
3 Compressor thermo. Bimetal
type (Model : PW - 2AL)
4 Outdoor temperature sensor
(TO), discharge temperature
sensor (TD), suction
temperature sensor (TS),
outdoor heat exchanger
temperature sensor (TE)
Checking procedure
Measure the resistance value of each winding by using the tester.
Measure the resistance value of winding by using the tester.
For details, refer to Section 10-9.
Check conduction by using the tester.
Disconnect the connector, and measure resistance value with the tester.
(Normal temperature)
TGa : Heat pump model only.
TO, TS, TE : Refer to the TA, TC characteristic table in Indoor (Refer to
Table 10-8-3, No. 1).
Temperature
10°C 20°C 30°C 40°C 50°C
Sensor
TD (k) 105 64 41 27 18
Brown
Red
Orange
Yellow
Pink
Blue
6
5
4
3
2
1
Position Resistance value
Red - White 0,51 to 0,57
White - Black 0,51 to 0,57
Black - Red 0,51 to 0,57
Under 20°C
Position Resistance value
Yellow- Pink 5 to 20 k
Red
White Black
Red
1 Yellow
4 Pink
5 Gray
White Black
10-8-3. Indoor Unit (Other Parts)
10-8-4. Outdoor Unit