Thermo Products OMC-70 Furnace User Manual


 
All installations and services must be performed by qualified service personnel.
31
V. DEALER MAINTENANCE
THIS SECTION IS ONLY TO BE PERFORMED BY TRAINED, QUALIFIED SERVICE
PERSONNEL, AND NOT BY THE FURNACE OWNER.
A. TROUBLESHOOTING
: When testing electrical equipment, always follow standard electrical procedures
and precautions.
1. Check for line voltage (110-120VAC) to the furnace. If there is no line voltage applied to
the furnace, check that disconnecting switch is “on”, fuses or circuit breakers have not
blown or tripped.
2. Make sure thermostat is “calling for heat”.
3. Check for adequate fuel supply and pressure. Are all the fuel shutoff valves are open?