Thermo Products ome-72d36 Furnace User Manual


 
All installations and services must be performed by qualified service personnel.
35
Is there combustion
airflow to the furnace?
Yes
Yes
Yes
Yes
Is there 120 VAC across
the burner motor?
Is the blower impeller spinning?
If so, check for blockages in or a
collapsed air duct. Is the air boot
shutter open adequately.
Yes
Check wiring to burner motor.
If okay, replace burner motor.
Correct wire connections.
Replace thermostat.
Are the thermostat wires
connected properly?
Yes
No
No No
No
Is the oil primary control
supplying 24 VAC to the
thermostat?
Try resetting the oil primary
control. Replace the oil
primary control, if necessary.
Is the oil primary
control receiving power?
Reset primary control. If
resetting the primary does
not work, replace control.