All installations and services must be performed by qualified service personnel.
32
M. FLUE GAS COMBUSTION ANALYSIS
: Burner adjustments must be confirmed by instrumentation. Failure to
use accurate or calibrated instrumentation to correctly setup the burner may result in
reduced efficiency, sooting, and/or the production of hazardous carbon monoxide gas.
For typical burner combustion analysis results, refer to the table below.
BURNER COMBUSTION PARAMETERS
FURNACE MODEL OME-72
LOW-FIRE
HIGH-FIRE
FUEL TYPE
#1 OR #2 FUEL OIL
#1 OR #2 FUEL OIL
CO (CARBON MONOXIDE)
50PPM OR LESS
50PPM OR LESS
CO2 (CARBON DIOXIDE)
10.5-11%
11-12%
O2 (OXYGEN)
4.5-6%
4.5-6%
SMOKE SPOT RATING
0
0
AIR SHUTTER ADJUSTMENT
OPEN TO POSITION 3.5
OPEN TO POSITION 3.5