Thermo Products ome-72d36 Furnace User Manual


 
All installations and services must be performed by qualified service personnel.
19
H. FUEL PIPING
Sizing and installation of fuel lines must be in accordance with federal, state and local
regulations.
1. Oil Tank and Piping
: All local codes and ordinances take precedence with regard to tank and oil lines.
All lines must have oil shutoff valves, a good pipe joint compound approved for use with oil on
all pipe threads, no kinks; no sharp bends and be properly tested for leaks. Flare fittings are
recommended for tubing.
: Do not run the oil pump dry for more than five minutes.
Your furnace is factory equipped to operate on No. 2 distillate fuel (domestic heating) oil. In very
cold weather, No. 1 distillate fuel oil may be used. Your oil supplier should be contacted for
recommendations.
: Do not use motor oil or any fuel heavier than No. 2 fuel oil..
Burners are most commonly installed with a single stage fuel pump (refer to Figure 7). This type
of fuel pump, when connected with a supply line only, is satisfactory where the fuel supply is
level with, or above, the burner. This type of installation permits gravity flow of oil to the burner.
When it is necessary to “lift” (raise) oil to the burner, a return line should be connected between
the fuel pump and tank. This requires insertion of the “by-pass” plug into the fuel pump. If the
lift exceeds approximately 10 feet, a two-stage pump should be installed with a return line. When
a return line is used with either single or two-stage pumps, air is automatically returned to the
tank, making the unit self-purging.
Use of continuous runs of heavy wall copper tubing is recommended. Always use flare fittings.
Avoid use of fittings in inaccessible locations. Avoid running tubing against any type of
heating unit and across ceiling or floor joists.
If possible, install the tubing under the floor. Specific information on piping, fuel pump
connections, lift capabilities and tank installations is provided in the fuel pump manufacturer’s
instructions.
If the oil tank is located inside the building and the tank capacity is between 10 and 660
gallons, it shall not be located within 5 feet horizontally from any source of heat, or oil-
burning appliance. Furthermore, the oil tank shall not block access to utility service
meters, switch panels, and shutoff valves.
If an underground tank used, the top of the tank should be below all piping in order to prevent oil
discharge through a broken connection. Underwriters Laboratories requirements now stipulate
that all 275 gallon and larger tanks have a bottom outlet. This is to prevent the accumulation of