System Sensor PDRP-1002 Series Home Security System User Manual


 
2. Installation Setting Mode of Operation
30
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Zone Relay Module Configuration
Relay #1, #2, #3 and #4 of the the 4XZM Zone Relay Module have specific functions based on the
configuration of DIP Switches #1 and #2 on the control panel. The table below provides a description of
these functions.
DIP #1 is OFF
(Either Zone)
DIP #1 is ON
(Cross Zone)\
DIP #2 is ON (Supervisory)
Either Zone Cross Zone
Relay #1
Activate when alarm
is detected in
Zone #1 or Zone #2
Activates when first
alarm is detected in
the system
Same
Same
Relay #2
Activates upon
second alarm
Same
Relay #3
Activates when
Release 1 is activated
Activates when
Release 1 is activated
Same Same
Relay #4
Activates when
Release 2 is activated
Activates when
Release 2 is activated
Not Used Not Used
Note: Relay #5 is reserved for General Alarm and Relay #6 is reserved for System Trouble.