System Sensor PDRP-1002 Series Home Security System User Manual


 
Installing Optional Voltmeter/Ammeter 2. Installation
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
15
Installing Optional Voltmeter/Ammeter
To monitor battery voltage and battery charging current, a 4XMM Meter Module is required. To install
the power meter module follow the steps below:
The figure below shows the mounting location and connections for the Voltmeter/Ammeter.
Figure 3 Mounting and Connecting the Meters
Step Action
1
Cut the jumper wire labeled “AMP”.
2 Secure the module to the backbox with the hardware provided. Refer to
Product Installation Drawing (PID) for detailed instructions.
3
Connect meter cable P2 to connector J2 on the main circuit board.
4
Connect meter cable P3 to connector J3 on the main circuit board.
J3
J9
J2
AMP
TB5
0
10 20
30
DC VOLTS
3
DC AMPERES
0
3
MS44-mminst.cdr
‘AMP’ Jumper