3.5.2. Entering dryer values
Select ”Dryer”.
Acknowledge with the ENTER-key.
or
Press the ”F3”-key.
Regeneration Heater Act.
The regenerated heat temperature will be displayed.
Used air Act.
The current temperature of the used air will be displayed.
Press the “â” key.
&
If the unit op er ates with “Dew point de pend ent re gen er a tion switch” (op -
tional):
Dew point max.
En ter the max i mum per mis si ble (worst al lowed) dew point tem per a ture (-35 to 28 °C) (-31 to
82.4°F)..
Ac knowl edge with the EN TER-key.
Dew point Act.
The cur rent dew point tem per a ture will be dis played.
&
If there is a ca ble break “+0 °C” (32°F) is dis played.
Press the “â” key.