Sterling Plumbing 225 Dehumidifier User Manual


 
Cabinet Series Dehumidifying Dryer 46
Option Type RE232C RS-485 Event Input Transfer Output
Board Number E53-CK01 E53-CK03 E53-CKB E53-CKF
Mode Parameter Setting range
Default
Factory
setting
Option Eu-A Multi-SP Function 0/1 0 Default
Option Eu-1 Event Input Assign 1 STOP/MAN STOP Default
Option SbCE Communication Stop Bit ½ BITS 2 Default
Option Len Comm. Data Length 7/8 BITS 7 Default
Option PrEY Commication Parity None/Even/Odd Even Default
Option 6PS Comm. Baud Rate 1.2/2.4/4.8/9.6/19.2 9.6 kbps Default
Option U-n6 Comm. Unit No. 0 to 99 0 Default
Option Er-E Transfer Output Type SP/SP-M/PV/O/C-O SP Default
Option Er-H Xfer Output Upper Limit 5 5 Default
Option Er-L Xfer Output Lower Limit 5 5 Default
Restoring Factory Defaults on the Dew Point Controller
1. Make sure jumper setting for input type is set for Current Input (I), right jumper.
2. Return controller to housing.
3. Press the Display button for one (1) second to enter Menu Display.
4. Press the Arrow Up button to switch between menus.
5. To switch parameters within a menu, press Up Arrow button.
Figure 9
Setting List for Dew Point Controller, Part No. A0548567
Mode Parameter Setting range Default Factory
setting
Protect SECr Security 0 to 6 1 3
Protect YEYP A/M Key Protect ON/OFF OFF ON
Manual Manual MV -5.0 to 105.0 % 0.0 Default
Level 0 SP Set Point SP lower limit to upper limit EU 0 Default
Level 0 r-S Run/Stop Run/Stop Run Default
Level 1 AL-1 Alarm Value 1 -1999 to 9999 EU 0
-10.0°F/-23°C
Level 1 AL-2 Alarm Value 2 -1999 to 9999 EU 0
-10.0°F/-23°C
Level 1 C-db Dead Band -19.99 to 99.99%FS 0.00 Default
Level 1 HYS Hysteresis (Heat) 0.01 to 99.99% FS 0.10 Default
Level 1 CHYS Hysteresis (Cool) 0.01 to 99.99 FS 0.10 Default
Level 2 SPrU Sp Ramp Time Unit M(Minutes)/H(Hours) M Default
Level 2 SPrt Sp Ramp Set Value 0 to 9999 EU 0 Default
Level 2 CnF Input Digital Filter 0 to 9999 SEC 0 Default
Level 2 ALH1 Alarm 1 Hysteresis 0.01 to 99.99% 0.02 Default
Level 2 ALH2 Alarm 2 Hysteresis 0.01 to 99.99% 0.02 Default
Level 2 Cn5H input shift upper limit
-199.9 to 999.9°C
0.0 Default