Sterling Plumbing 225 Dehumidifier User Manual


 
Cabinet Series Dehumidifying Dryer 43
2. Make sure jumper setting for input type is set for thermocouple TC-PT, middle jumper.
3. Return controller to housing.
4. Press the Display button for one (1) second to enter Menu Display.
5. Press the Up Arrow button to get to Setup mode.
6. To switch parameters within Setup mode, press the Display button.
Figure 8:
Setting List for Process Temperature Controller, Part No. A0548565
Mode Parameter Setting range Default Factory
setting
Protect SECr Security 0 to 6 1 5
Protect YEYP A/M Key Protect ON/OFF OFF ON
Manual Manual MV -5.0 to 105.0% 0.0 Default
Mode Parameter Setting range Default Factory
setting
Level 0 SP Set Point SP Lower Limit to Upper Limit EU 0 Default
Level 0 r-S Run/Stop Run/Stop Run Default
Level 1 SP-0 Set Point 0 SP Lower to Upper EU 0 Default
Level 1 SP-1 Set Point 1 SP Lower to Upper EU 0 Default
Level 1 AL-1 Alarm Value 1 -1999 to 9999 EU 0 25.0
Level 1 AL-2 Alarm Value 2 -1999 to 9999 EU 0 25.0
Level 1 AL-3 Alarm Value 3 -1999 to 9999 EU 0 Default
Level 1 P Proportional Band 0.1 to 999.9% FS 10.0 4.4
Level 1 I Integral Time 0 to 3999 SEC 233 84
Level 1 d Derivative Timer 0 to 3999 SEC 40 13
Level 1 C-SC Cooling
Coefficient
0.01 to 99.99 1.00 Default
Level 1 C-db Dead Band -19.99 to 99.99%FS 0.00 Default
Level 1 6F-r Manual Reset
Value
0.0 to 100.0% 50.0 Default
Level 1 HYS Hysteresis (Heat) 0.01 to 99.99%FS 0.10 Default
Level 1 CHYS Hysteresis (Cool) 0.01 to 99.99%FS 0.10 Default
Level 1 CP Control Period
(Heat)
1 to 99 SEC 20 Default
Level 1 C-CP Control Period
(Cool)
1 to 99 SEC 20 Default
Mode Parameter Setting range Default Factory
setting
Level 0 SP Set Point SP Lower Limit to Upper Limit EU 0 Default
Level 0 r-S Run/Stop Run/Stop Run Default
Level 1 SP-0 Set Point 0 SP Lower to Upper EU 0 Default
Level 1 SP-1 Set Point 1 SP Lower to Upper EU 0 Default
Level 1 AL-1 Alarm Value 1 -1999 to 9999 EU 0 25.0