State Industries SUF-130- 300/400/500 Water Heater User Manual


 
29



        

     



NOTE: SECURING STRAP
MUST BE FIELD INSTALLED
TO PREVENT MOVEMENT
OF TERMINATION KIT
MAINTAIN 12” (30 cm)
18” (45 cm) FOR CANADA
MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL. MAXIMUM OF
24” (60 cm) ABOVE ROOF.
ROOF FLASHING
(field supplied)
STRAP
(field supplied)
VENT
PIPE
INTAKE
AIR PIPE
COMBUSTION
AIR
VENT
6 INCH CONCENTRIC TERMINATION
VERTICAL INSTALLATION
Figure 30
NOTE: SECURING STRAP MUST BE
FIELD INSTALLED TO PREVENT
MOVEMENT OF TERMINATION KIT
IN SIDEWALL.
STRAP
(field supplied)
VENT
PIPE
INTAKE
AIR PIPE
COMBUSTION
AIR
VENT
1 INCH
MAXIMUM
6 INCH CONCENTRIC TERMINATION
SIDEWALL INSTALLATION
Figure 31



         


6 INCH CONCENTRIC TERMINATION INSTALLATION
6 INCH CONCENTRIC TERMINATION KIT
SEVEN PIECE KIT - FIELD ASSEMBLY REQUIRED
VENT PIPE
VENT PIPE IS 4 INCH SCHEDULE 40 PVC
SUPPLIED LENGTH 46 1/2 INCHES (118 cm)
MAXIMUM ALLOWABLE LENGTH 66 1/2 INCHES (169 cm)
MINIMUM ALLOWABLE LENGTH 33 1/8 INCHES (84 cm)
INTAKE AIR PIPE IS 6 INCH SCHEDULE 40 PVC
SUPPLIED LENGTH 25 3/8 INCHES (64 cm)
MAXIMUM ALLOWABLE LENGTH 45 3/8 INCHES (115 cm)
MINIMUM ALLOWABLE LENGTH 12 INCHES (30 cm)
VENT CAP
STAINLESS STEEL
VENT TERMINAL
WITH SCREEN
INTAKE AIR PIPE
INTAKE AIR CONNECTION
6” or 4” PVC
VENT
CONNECTION
4” PVC
6” x 4” STANDARD
REDUCER BUSHING
6” x 6” x 6”
Y FITTING
6” x 4” NO STOP-LIP
REDUCER BUSHING
INTAKE AIR PIPE
Y FITTING ASSEMBLY
VENT CAP
VENT PIPE ASSEMBLY
Figure 29


 
           

 


 


 

  

 

 
         

 
 



    


