TROUBLESHOOTING
Technical Training Department State Water Heaters
STC-077
28 Ashland City, Tennessee © 2004
120 VAC TO IGNITOR
STEP 10: CHECK FOR 120 VAC TO IGNITOR FROM PIN 1 AND 2 ON CONTROL BOARD
TERMINAL CN5.
Condition:
Disconnect CN5 plug from control board.
On/Off switch is on.
Call for heat is activated.
Perform test during ignitor warm up period.
STEP 10
120 VAC TO IGNITOR
IF... THEN
120 VAC is not present
replace the control board if Steps 7 through 9B have
been performed and results were successful.
120 VAC is present continue to step 11.