TEST 3 - CONTINUITY CHECK OF HIGH LIMIT (ECO)
Conditions:
Power On – No Hot Water
Red, heater control “Call for Heat”
LED – on
Red ignition control board
diagnostic LED – 4 Flashing
Note LED Flash Code before
resetting water heater control.
See Description of diagnostic LED
Flashes.
Turn Power “Off”
0.0
Ohms
TEST 3
Continuity check of ECO (energy cut-off, high limit)
Black to Black wires of upper probe. Power is off.
.....neht fI
continuity is indicated (ZERO “0.0” Resistance) opens at 203° F; closes at 193° F. If water is
below 193° F, continuity is correct.
continuity is not present (meter reads “0.L”) replace ECO sensor, if water temperature is
below 193° F.
.no eb dluohs DEL sutats teserF °021 naht ssel si retaw
•replace heater control if control will not manually
reset.