Specifications: Base
4
1.0 Base:
1.1 Provide an induced draft, crossflow
type, factory assembled, film fill,
industrial duty, stainless steel cooling
tower situated as shown on the plans.
The limiting overall dimensions of
the tower shall be _____ wide, _____
long, and _____ high. Total operating
kilowatt of all fans shall not exceed
____ kW, consisting of ___ @ _____
kW motor(s). Tower shall be similar and
equal in all respects to Marley Model
____________.
Your specification base establishes the type, configuration, base materi-
al and physical limitations of the cooling tower to be quoted. During the
planning and layout stages of your project, you will have focused your
attention on a cooling tower selection that fits your space allotment,
and whose power usage is acceptable. Limitations on physical size and
total operating horsepower avoid the introduction of unforeseen opera-
tional and site-related influences. Specifying the number of cells, and
the maximum fan kW/cell will work to your advantage.
The benefit of crossflow towers is that they are inherently easy to oper-
ate, access and maintain. Compared to counterflow towers, crossflow
towers have a spacious plenum between banks of fill for easy access to
all of the tower’s internal components, plus the water distribution sys-
tem is adjacent to the fan deck and can be maintained during operation.
The NC is also available unassembled for on-site assembly.