Specifications
Specification Value
Marley
/
NC Class Stainless Cooling Tower
/
Specifications: Options
13
Access Door Platform:
11.2 Add the following paragraph in the
Access section: There shall be an
access platform at the base of the
tower extending from the vertical lad-
der to the endwall access door. The
platform shall be galvanized steel bar
grating, supported by galvanized steel
framework attached to the tower.
The platform shall be surrounded by a
guardrail, kneerail, and toeboard.
Plenum Walkway
11.2 Add the following paragraph in the
Access section: Provide a factory-
installed, galvanized steel bar grating
walkway extending from one endwall
access door to the other endwall. This
walkway shall be supported by a gal-
vanized steel framework, and the top
of the grating shall be at or above the
cold water basin overflow level.
Interior Mechanical Equipment
Access Platform
NC8303 thru NC8309
11.2 Add the following paragraph in the
Access section: A factory-installed,
elevated galvanized bar grating plat-
form convenient to the care and main-
tenance of the tower's mechanical
equipment shall be provided.
Interior Mechanical Equipment
Access Platform
NC8310 thru NC8312
11.2 Add the following paragraph in the
Access section: An internal ladder
shall extend upward from the plenum
walkway to an elevated galvanized
bar grating platform convenient to the
care and maintenance of the tower's
mechanical equipment. The platform
shall be surrounded by a sturdy guard-
rail and kneerail system.
■ Where towers are installed on an elevated grillage or piers, it is
often difficult to get to—and through—the access door conve-
niently. This platform provides easy, safe and comfortable access
to that door. It also extends beyond the door to provide ready
access to the optional Control System. See drawing on page 12.
Outside the tower, stainless steel platform material is not normal-
ly considered necessary. If you air quality is sufficiently poor to
warrant stainless steel, change the specification wording accord-
ingly.
NOTE
OSHA and other concerned authorities are in the process
of developing guidelines regarding the safety procedures and
protective equipment that should be provided maintenance per-
sonnel who are required to go inside cooling towers. We feel it
advisable to provide for as much maintenance as possible from
outside the cooling tower and, to that end, offer such options as
Guardrail and Ladder—pg 11, Ladder Extension—pg 11, Ladder
Safety Cage—pg 11, Access Door Platform—pg 13, and Motor
Out of the Airstream—pg 18. Such interior convenience options
as Plenum Walkway—pg 13, that are offered are not meant as
an invitation to perform inside maintenance. They are intended
solely to maximize the comfort and safety of maintenance per-
sonnel during the performance of any inside work may become
necessary.