PIPING A HEATING - COOLING SYSTEM TO A WATER
BOILER AND CHILLER
The chiller must be piped in parallel with the boiler. Figure below
illustrates a method of piping a heating-cooling system to a
water boiler and a chiller. Hand valves (shown) or automatic
valves must be installed to prevent circulation of chilled water in
t
he boiler or hot water in the chiller.
The air control system and pressure control system must oper-
ate with chiller only, or the boiler only, being valved to the piping
system.
Separate control devices on the boiler and chiller may be used,
or a single set of air and pressure controls on the common pip-
ing may be preferred.
If the boiler is used to supply hot water to heating coils in air
handling units, flow control valves or other devices must be
installed to prevent gravity circulation of water in the coils dur-
ing the cooling cycle.
IF REPLACEMENT PARTS ARE NEEDED
When parts are needed, refer to boiler model and serial num-
ber shown on the boiler name/rating plate. Refer to publication
number S-10PL Sentry Replacement Parts for part numbers.
Whenever possible refer to the original order by number and
date.
Control identification and replacement should not be attempted
by unskilled personnel. Only simple, easily-identified controls
and parts may be obtained locally. All other controls and
parts should be identified by and ordered from Slant/Fin.
Relief/Safety valves must be ASME rated for the pressure and
gross output of the boiler.
For replacement parts, heating contractors should contact their
Slant/Fin boiler distributor.