Simer Pumps 2825SS Water Pump User Manual


 
Operation 6
For parts or assistance, call Simer Customer Service at 1-800-468-7867 / 1-800-546-7867
2. Replace all fill plugs.
3. Power on! Start the pump. If you don’t have water
after 2 or 3 minutes, stop the pump and remove the
fill plugs. Refill the pump and piping. You may have
to repeat this several times in order to get all of the
trapped air out of the piping. A pump lifting water 25’
may take as long as 15 minutes to prime.
4. After the pump has built up pressure in the system
and shut off, check the pressure switch operation by
opening a faucet or two and running enough water
out to bleed off pressure until the pump starts. The
pump should start when the pressure drops to 30 PSI
and stop when the pressure reaches 50 PSI. Run the
pump through one or two complete cycles to verify
correct operation. This will also help clean the system
of dirt and scale dislodged during installation.
Congratulations on a successful installation.
If you were unsuccessful, please refer to the
Troubleshooting section (below) or call our customer ser-
vice technical staff at 1-800-468-7867.
Troubleshooting
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
Motor will not run Fuse is blown or circuit breaker tripped DISCONNECT POWER;Replace fuse or reset circuit breaker.
Motor runs hot and Voltage is too low Check voltage being supplied to the pump.
the overload kicks
off or the does not
run and only hums.
Motor runs but no Pump during new installation did In new installation:
water is delivered* not pick up prime through:
1. Improper priming 1. Re-prime according to instructions.
2. Air leaks 2. Check all connections on suction line, with soapy water or
shaving cream.
3. Leaking foot valve 3. Replace foot valve.
4. Pipe size is too small 4. Re-pipe using size of suction and discharge ports on pump.
Pump has lost prime through: In installation already in use:
1. Air leaks 1. Check all connections on suction line and shaft seal with soapy water.
2. Water level below suction pipe inlet 2. Lower suction line into water and re-prime. If receding water level
in well exceeds 25’ (7.6M), a deep well pump is needed.
Impeller is plugged Clean impeller.
Foot valve is stuck shut Replace the foot valve.
Pipes are frozen Thaw pipes.
Foot valve and/or strainer are Raise the foot valve and/or strainer above bottom of water source.
buried in sand or mud Clean foot valve and strainer.
*Pump does not Water being pumped is lower than A deep well jet will may needed if the water being pumped is more than
deliver water to full estimated 25’ (7.6M) depth to water.
capacity
Steel piping (if used) is corroded or Replace with plastic pipe where possible, otherwise with new steel pipe.
limed, causing excess friction
Piping is too small in size Re-pipe using size of suction and discharge ports on pump.
Pump not being supplied with Add additional well points.
enough water
* (Note:
Stop pump;
then check prime
before looking for
other causes.
Unscrew
priming
plug and see if water
is in priming hole).