Sears 583.35682 Electric Heater User Manual


 
100506
VENTILATION
OPERATION
WARNING
Follow the minimum fresh, outside air ventilation
requirements. If proper fresh, outside air ventilation is not
provided, carbon monoxide poisoning can occur. Provide
proper fresh, outside air ventilation before running heater.
Provide a fresh air opening of at least three square feet for each 100,000 Btu!Hr
rating. Provide extra fresh air if more heaters are being used.
Example: A 110,000 Btu!Hr heater requires one of the following:
a two-car garage door raised three inches
a single-car garage door raised five inches
two thirty-inch windows raised eight inches
IMPORTANT
Review and understand the warnings in the Safety Information Section.
They are needed to safely operate this heater. Follow all local codes
when using this heater.
To Start Heater
l. Follow all ventilation and safety information.
2. Fill fuel tank with kerosene or No. 1 fuel oil.
3. Attach fuel cap.
4. Plug power cord of heater into three-prong, grounded extension cord. Exten-
sion cord must be at least six feet long.
.
Extension Cord Wire Size Requirements
6 to l0 feet long, use 18 AWG rated cord
11 to 100 feet long, use 16 AWG rated cord
101 to 200 feet long, use 14 AWG rated cord
Plug extension cord into standard 120 volt/60 hertz, three-hole, grounded
outlet. Heater will start when extension cord is plugged into outlet. If not,
push in flame-out control reset button (see Figures 5 and 6).
Flame-
Out
Reset
Button
Flame-Out
Control
Reset
Button
Figure 5 - Flame-Out Control Reset
Button, 35/55,000 Btu/Hr Models
Figure 6 - Flame-Out Control Reset
Button, 110, 000 Btu/Hr Model
Continued