Sanyo KH3672R / C3672R Air Conditioner User Manual


 
I-89
SM831148
1. Specifications
1
2
3
4
5
6
Fig. 1-4
Anchor bolts
(4 pieces)
Fig. 1-1
Out-
door
unit
Heat source
Hot air
Exhaust fan
*4*2
*3
*1
More than 25/64"
More than
3.3 ft.
More than 25/64"
Inlet side C
Outlet side
Fig. 1-2
Fig. 1-3
*1
Inlet side
More than 8"
(field supply)
A
B
(Ground)
Air direction chamber
(Obstruction above unit)
(Obstruction on
inlet side)
CAUTION
Concerning inlet-side distance C (Fig. 1-2)
The minimum for distance C is 6" if there are no obstructions on the outlet side
(wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance
C is 8".
If the unit is installed with the outlet side facing wall *1, then there must be no obstruc-
tions on 2 of the remaining 3 sides: *2, *3, *4.
If wall *1 is on the outlet side (Fig. 1-2), or if obstructions are present on all 3 sides *2,
*3, and *4 (Fig. 1-2), then the minimum distance for A and B is 80" (Fig. 1-3). Even if
there is no wall on the outlet side, a minimum of 3.3 ft. is required.
Installation requirements
provide a solid base (concrete block, 4" × 16"
beams or equal), a minimum of 6" above ground
level to reduce humidity and protect the unit gainst
possible water damage and decreased service life.
(Fig. 1-4)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 1-1)
damp, humid or uneven locations
DO:
choose a place as cool as possible.
choose a place that is well ventilated and outside air
temperature does not exceed maximum 115°F
constantly.
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 1-2)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
if cooling operation is to be used when the outdoor
air temperature is 23°F or below, install a duct on the
outdoor unit.
Installation space
Distance between obstructions and the unit air inlet and
outlet must be as shown below.