Sanyo CL1852 Air Conditioner User Manual


 
– 22 –
SM830079
8. ELECTRICAL DATA
Indoor Unit Outdoor Unit
Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
Rating conditions
A 0.60 - 0.60 0.5 - 0.5 7.1 - 7.7 8.2 - 8.77
kW 0.12 - 0.11 0.11 - 0.10 1.56 - 1.53 1.79 - 1.74
Full load conditions
A 0.60 - 0.60 0.5 - 0.5 8.4 - 9.5 9.7 - 10.57
kW 0.12 - 0.11 0.11 - 0.10 1.93 - 1.96 2.16 - 2.17
Starting amperes A 1 - 1 0.7 - 0.6 43 - 43 44.7 - 44.6
Rating Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 95 °F DB
Full Load Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 115 °F DB
Electrical characteristics
Indoor model: XS1852 / Outdoor model: C1852, CL1852