Samsung AM27B1C13 Air Conditioner User Manual


 
E-45
ENGLISH
Connecting Up and Purging the Circuit
COMPLETING THE INSTALLATION
A
B
C
D
Outdoor unit Indoor unit
Gas pipe side
Liquid pipe side
The outdoor unit is loaded with sufficient R22 refrigerant for 5m(16ft. 5in) of
piping. The air in the indoor unit and in the pipe must be purged.
If air remains in the refrigeration pipes, it will affect the compressor,
reduce to cooling capacity and could lead to a malfunction.
Refrigerant for air purging is not charged in the outdoor unit.
Use Vacuum Pump as shown at the figure.
1 Connect each assembly pipe to the appropriate valve on the outdoor unit
and tighten the flare nut.
2 Referring to the illustration opposite, tighten the flare nut first manually
and then with a wrench, applying the following torque.
3 Connect the charging hose of low pressure side of manifold gauge to the
packed valve having a service port as shown at the figure.
4 Open the valve of the low pressure side of manifold gauge
counterclockwise.
5 Purge the air from the system using vacuum pump for about 10 minutes.
-
Close the valve of the low pressure side of manifold gauge clockwise.
-
Make sure that pressure gauge show -0.1MPa(-76cmHg) after about
-
10minutes.
-
This procedure is very important in order to avoid gas leak.
-
Turn off the vacuum pump
-
Remove the hose of the low pressure side of manifold gauge.
6 Set valve cork of both liquid side and gas side of packed valve to the open
position.
7 Mount the valve stem nuts and the service port cap to the valve, and
tighten them at the torque of 18N
m with a torque wrench.
8 Check for gas leakage.
-
At this time, especially check for gas leakage from the 3-way valves
stem nuts, and from the service port cap.
You can install 15m of connecting pipe to the maximum, and you don’t have
to charge any additional refrigerant.
Pipe Outer Diameter Torque
Liquid refrigerant 6.35 mm(1/4˝) 160kgcm(11.6ftlb )
Gas refrigerant 9.52 mm(3/8˝) 300kgcm(21.8ftlb )
Gas refrigerant 12.70 mm(1/2˝) 500kgcm(36.4ftlb )
Liquid side
Valve stem
Stem cap
Gas side
Service port
A
B
Vacuum Pump
Indoor
A-unit
Indoor
B-unit
The designs and shape are subject to
change according to the model.