Roberts Gorden HP 230 V 1 Gas Heater User Manual


 
SYSTEM CONTROL INSTALLATION, OPERATION AND SERVICE MANUAL
8
FIGURE 6: External Wiring Diagram ROBERTS GORDON
®
EP-100, EP-201 or EP-301, 230 V 1 Ø Pump
4.2 EP-201 or EP-301 230 V 1 Ø External Wiring
Diagram
The external wiring diagram above shows the
connections for four zones of system burners.
System burners can be either CORAYVAC
®
or VAN-
TAGE
®
NP (multiburner only).
The zones are connected to a single pump, unless
zone 3 and/or zone 4 are selected to function with
the optional pump 2. The external wiring diagram
above shows connection to an EP 301 or EP-201 1 Ø
pump.
4.2.1 External Wiring Connection Details
The cable used for all the wiring must be rated for
line voltage up to 600 Vac.
The low voltage circuit conforms with Class 2 separa-
tion of circuit requirements. National Electrical Codes
®
for wiring class 2 low voltage circuits must be followed.
System Control
R R R R PS 2PS 124 VAC
COM
24 VAC
COM
PS 1 PS 2WWWW
24 VAC
120 V
1 Ø
60 Hz
Ground
G
L
N
120 V
1 Ø
60 Hz
PUMP 2PUMP 1
POWER
SUPPLY
N
L
Z1
Z2
Z3 Z4
N
N
N
NLL
L
L
All burners must be
connected to Ground
(Not shown)
Zone 1
Zone 2 Zone 3 Zone 4
EP-100,
EP-201 or
EP-301 Pump
N
L
L
N
TWO PUMP SYSTEM (optional)
Pump 1 may be used for all zones.
Pump 2 may be used to control zone 3
and/or zone 4. Refer to Pump 1 for configuration.
Low voltage thermostats
located in heated zone
Zone
1
Zone
2
Zone
4
Zone
3
Pressure
switch
located at
pump 2
Pressure
switch
located at
pump 1
208 - 230 V
1 Ø
60 Hz
L2
L1
M
1
5
3
2
64
Individual supply for
pump rated for total full
load current. See Section
2.3 for details.
EP-100, EP-201 or
EP-301 Pump
The power supply for the
pump must be separate
from the controller supply
Motor Contactors
P/N 10050011
P/N 10050012
CAUTION
Product Damage Hazard
Do not directly connect control relay terminals
to pump motor
.
Failure to follow these instructions can result
in product damage.