Rinnai E110CP Boiler User Manual


 
Installation & Servicing Instructions Rinnai E-Series
48
Service Mode
SERV
VALUE
DESCRIPTION
RANGE
1 OFF boiler in operation with burner function o
n
OFF - max.
2 OFF fan adjustable and burner of
f
OFF - max.
3 OFF pump adjustable with burner o
n
OFF - max.
4 OFF showroom position ON = active and OFF = non active ON - OFF
. . . .
Error Mode
ERRO
VALUE
DESCRIPTION
Err.L - Err.5 Last saved error until 5 last previous error
s
1 error cod
e
2 operation status boile
r
3 °F supply water temperature T1
4 °F return water temperature T
2
5 kW load (.. x3415 = .. BTU/hr)
6 % pump capacity
* Most of the data in this table can be requested by the RS100. Most of the
adjustments which are stated in this table are unnecessary when in combina-
tion with the Rinnai RS100 thermostat and will be taken care of by the RS100
itself and do not have to be adjusted. For further information regarding to the
RS100 thermostat refer to the Rinnai RS100 installation manual.
Parameter-, Info-, Service- and Error-chapters Table 12
NOTICE
i
heating line adjustments Parameter Step 6 and 7 graph 2
outside temperature in °F
ow water temperature in °F
Outdoor reset
Heat curve day
Heat curve night
230
212
194
176
158
140
122
104
86
68
50
-4.0
-0.4
3.2
6.8
10.4
14.0
17.6
21.2
24.8
28.4
32.0
35.6
39.2
42.8
46.4
50.0
53.6
57.2
60.8
64.4
68.0
2.30
1.50
1.00
1.00
0.50
1.80
2.00
1.75