Regency P121/P131-NG2 Indoor Fireplace User Manual


 
Framing and Finishing
1) Determine the total thickness of facing material (e.g. drywall plus
ceramic tiles) to allow the fi nished surface to be fl ush with the front
of the unit. Total facing thickness can vary from 1/2” (13mm) to 1-¼”
(32mm) thick.
2) Frame in the enclosure for the unit with framing material.
3) For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapor barrier and drywall, as per local
installation codes. (Do not insulate the fi replace itself.)
4) The top of the unit must not be closer than 36” (990mm) to the
ceiling.
5) Combustible material may be brought up to the top and
sides of the unit and be covered with ceramic tiles, bricks,
rock or other suitable combustible finishing materials.
Note: The unit does not have to be completely enclosed in a
chase. The clearance on top of the unit is 0” to the standoffs
so combustible building materials can be laid directly on top
of the standoffs. You must maintain proper clearances from
the vent to combustible materials (See Below).
6) Use metal studs for framing where the minimum clearance from
the vent to combustible material cannot be maintained.
Drywall
Mantel Clearances
2
0
12
6
4
810
0
Side View
To po f
Unit
12" (305mm)
3 ½" (89mm)
A
Standoff
B
C
Header
3” Extension Trim
Mantel Clearances
ABC
Front 36” (914mm) 7” (178mm) 3” (76mm)
P121-P131 Gas Fireplace
Combustible Mantels
Because of the extreme heat this fi replace emits, the mantel
clearances are critical. Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed
anywhere in the shaded area or higher.
Note: If desired a non-combustible mantel may be installed at a
lower height.
Note: Ensure the paint that is used on the mantel and the facing
is “heat resistant” or the paint may discolour.
Note: If the fi replace is installed
without the 3” Extension Trim,
the facing material must be
non combustible up to 8”
above the unit.
36"min.
(914mm)
36"min.
(914mm)
36"min. (914mm)
Parallel Wall Clearances
Unless otherwise stated the clearances listed below are Minimum
distances to combustible materials. Unit pictured is a P131
Parallel Wall Clearances P121(LC/RC)/131
Min distance from glass to a parallel wall 36” (914mm)
WARNING
Failure to maintain required clearances is a major cause of
chimney related fi res. Installation of this fi replace must comply
with these clearances.
Clearance: Dimension Measured From:
A: Mantel Height 3” (76mm) Minimum (Additional on this page)
B: Sidewall 0” (0mm) Side of installed front
3” (76mm) On P121-2 See-Thru
3” clearance opposite vent.
C: Ceiling 36” (914mm) Top of installed unit
D: Mantel Depth 12” (305mm) Maximum (Additional on this page)
E: Alcove Width See Parallel Wall Clearances.
F: Alcove Depth 36” (914mm) Front to back wall (Maximum)
Top of Hearth must not be higher than the base of the fi rebox.
Vent Clearances Clearance Dimension
Horizontal - Top 2-1/2” (64mm)
Horizontal - Side 1-1/2” (38mm)
Horizontal - Bottom 1-1/2” (38mm)
Vertical 1-1/4” (32mm)
E
B
B
A
C
D
F
Clearance Requirements
70 June 2007 Regency Product Specifi cations Book
Gas Fireplaces
Gas Fireplaces