Regency FG39-NG Stove User Manual


 
10
Regency FG39 FireGenie Freestanding Gas Stove
INSTALLATION
DV STOVE HORIZONTAL FLUE KIT (#946-112) INSTALLATION
Minimum Installation Height:
FG39: 59-3/4" ( 1518mm)
Review the following sequence of instruc-
tions which are typical of most installations.
The sequence may vary depending on wall
thickness. Refer to flue location and clear-
ance dimensions on pages 8 to 9.
1) Set the unit in its desired location. Check
to determine if wall studs will be in the way
of the fluing system, adjust location until all
clearances are met and there are no
obstructions.
Note: A 1-1/2"(38mm) clearance around
the outer pipe must be main-
tained except that only a 1"
(25mm) clearance is needed at
the termination end.
IMPORTANT:
Do not locate termination hood where
excessive snow or ice buildup may oc-
cur. Be sure to check flue termination
area after snow falls, and clear to pre-
vent accidental blockage of fluing sys-
tem. When using snow blowers, make
sure snow is not directed towards flue
termination area.
2) Assemble a trial fit to determine the ver-
tical center-line for the flue termination.
a) Cut a 241mm round hole on both the
interior and exterior wall.
b) Attach the 2 ft. (.6m) pipe section to
the flue terminal and slide into posi-
tion from the exterior. The larger
diameter end of the adjustable
pipe goes to the flue terminal.
c) Install the 90
o
elbow onto the adjust-
able pipe to determine the vertical
centerline of the starter collar on the
unit.
Note: if the centerline cannot be
met, the adjustable sections will
have to be cut.
DV STOVE HORIZONTAL FLUE KIT
Horizontal Stove Flue Kit (Part # 946-112) includes all the parts needed to install the FG39
Freestanding Gas unit with minimum horizontal and vertical vent dimensions. For installations that
require longer vertical and/or horizontal vents use the Dura-Vent system as shown in your manual.
Qty. Description
1) 2 Rigid Pipe Section 1.2m length, 165mm inside diameter
2) 1 Flex Liner, compressed aluminium 2 ply liner, 102mm inside diameter
3) 4 spring spacers
4) 1 90 deg. Elbow
5) 1 Decorative Wall Trim
6) 1 Adapter
7) 1 AstroCap Termination Cap
8) 2 Trim Collar
9) 1 tube of Mill-Pac, high temperature sealant
10) 12 Screws, #8 x 1/2" (13mm) Self tapping, Stainless Steel
11) 14 Screws, #8 x 1/2" (13mm) Self tapping, Black
12) 4 Screws #8 x 1-1/2" (38mm) Drill Point, Stainless Steel
Optional:
946-206 Vinyl Siding Standoff for AstroCap
Note:
a) Liner sections should be continuous
without any joints or seams.
b) This is an approved system, therefore
components in this system must not be
substituted for any other manufactur-
er's products.
c) Wall Thimble is required when install-
ing through a combustible wall.